Supports sv 110 on metal piles. Buy reinforced concrete poles for power lines at a price from the manufacturer. Direct deliveries across Russia. wind pressure in areas I-V

SV 110-5 supports made of reinforced concrete are used in the reconstruction and construction of power lines. The voltage of such a network should vary in the range from 0.4 to 10 kV. The product is also suitable for creating lighting for roads, parking lots, pedestrian infrastructure, and other objects in the city and beyond.

Characteristics of reinforced concrete pillars of supports SV 110-5

The trapezoidal column is made of concrete, additionally reinforced with steel reinforcement. With a mass of about 1125 kg, the geometric volume is 0.5698 cubic meters. The creation of one such element takes about 0.45 m 3 of concrete. Compliance with the proportions in the manufacture allows you to achieve a calculated bending moment equal to 5 tf * m.

Among the main product parameters:

  • Frost resistance F200. This helps to withstand the harsh conditions of the Russian winter, endure more than 200 freeze and thaw cycles. The product does not deteriorate even at a temperature of -55 0 C, as well as at high humidity in summer.
  • Water resistance W6-8. The material does not absorb water, retains its properties for a long time.
  • Concrete class B30. This indicates increased strength. The product withstands vibration, vertical loads, mechanical shocks without cracking and crumbling.

Racks SV 110-5 at manufacturer's price

To buy supports for power transmission lines SV 110-5, leave a request on our website. The ZHBI TORG company delivers production made on modern production. This helps us to control the quality, quickly ship and deliver orders. All products are certified and comply with GOST 23613-79. Products with other height and bending moment are also supplied to customers.

Racks reinforced concrete SV 110-5 (power line 98.16) widely used in various fields of construction and thermal power engineering. Without these elements, many areas cannot be fully mastered, since the high strength and reliability of reinforced concrete has not yet found its worthy replacement. That's whyracks SV 110-5 (power line 98.16) for power transmission towers are used without fail. These are conical reinforced concrete poles of variable section, which are used to support power lines.

The use of only wooden supports is not economically justified, since wood, even with special processing, does not last as long as reinforced concrete, while it should be noted that this material can be used on "difficult" soils and in aggressive operating conditions.

1. Variants of writing product labeling.

Racks SV 110-5 (power line 98.16) , made of reinforced concrete, are made according toGOST 23613-79 and Series 3.407.1-136 , all conditions must be met. The marking includes a special designation, which indicates the type of product and its size groups. Writing is not strictly regulated and can be done in several ways:

1. SV 110-5;

2. SV 110-5 IV;

3. SV 110-5 AM;

4. SV 110-5 a;

5. SV 110-5-4;

6. SV 110-6.

2. The main scope.

Reinforced concrete vibrated racks SV 110-5 (power line 98.16) are developed and used in the laying and arrangement of power lines with a voltage of 0.4-10 kW, as well as in the installation work of lighting networks. These products can be used in various environments, including in conditions of increased seismic activity (up to 7-9 points on the Richter scale), as well as in windy areas of l-lV type, as well as in icy conditions.

deepen transitionalracks SV 110-5 (power line 98.16) It is possible in various soils, including those with high acidity. Since the racks undergo special processing, they serve for a long time without collapsing and without losing their performance characteristics.SV 110-5 (power line 98.16) used for such types of supports as anchor-angular and intermediate, on which the wires of overhead power lines are suspended.

Reinforced concrete pillars perceive significant loads, mainly tearing deformations, therefore, special concretes are used for the manufacturing technology of these elements, as well as to comply with the requirements for strength and durabilityracks SV 110-5 (power line 98.16) made unified. The declared service life of vibrated racks is not less than 50-75 years. Besides,reinforced concrete racks depending on the conditions and requirements of the project, products such as cylindrical anchors AC-1 and support-anchor plates type P are used together.

3. Designation of product marking.

Reinforced concrete poles for power transmission lines SV 110-5 (LEP 98.16) marked according to the current Standard -Series 3.407.1-136 and GOST 23613-79 , indicate the type of product SV - the stand is vibrated, and the size group -11000x185x280, where:

1. 11000 - length or nominal height of the product;

2. 185x280 - section of the product.

Additionally, parameters such as:

1. Estimated bending moment - 5 ton*m;

2. Geometric volume -0,5698 ;

3. Product weight -1180 ;

4. The volume of concrete per column is0,45 .

The marking is applied to the side of the rack with indelible black paint, the date of manufacture of the batch, the manufacturer's trademark and the mass of the element are additionally applied.

4. Materials and characteristics of products.

Reinforced concrete racks are made using vibrocompression technology. Due to the high compaction of the concrete mixture, products are obtained with high strength characteristics. Heavy concrete, fine sand and crushed granite are used as raw materials. All this allows to increase frost resistance and reliability.racks SV 110-5 (power line 98.16) during long-term operation.

The main characteristics of concrete according toGOST 26633 , as well as in accordance with the established requirementsTU 5863-002-00113557-94 :

1. Brand for compressive strength - M300;

2. Concrete strength class - not less than B25;

3. Frost resistance - 200 freeze-thaw cycles, application can be carried out at critically low temperatures, up to -55 degrees Celsius inclusive;

4. Water resistance - W4 grade, additionally perform hydrophobic protection.

For durabilitySV 110-5 (power line 98.16) reinforce according toGOST 23613-79 . As reinforcement, prestressed steel bars of class A-III, At-I, At-VI, At-V with a diameter of 10-14 mm are used. (non-corrosive metal for external hinges and embedded parts - bolts with which the products are attached to the foundation). The lower part of the product uses wire reinforcement with a reverse taper. Steel and concrete are treated with special anti-corrosion compounds.

Power transmission line poles made of reinforced concrete have significant advantages over other building materials (there are also wooden and metal poles). Reinforced concrete is not subject to destruction under aggressive environmental influences and does not harm the environment; reinforced concrete products are suitable for installation even near clean groundwater sources. High strength and resistance to the environment (climatic conditions, precipitation and chemicals in the air) make it possible to expose racks to CB 110-3.5 IV for poles of 10kV transmission lines for non-aggressive and aggressive environments of long-term operation (50-70 years), while the construction of poles do not require constant maintenance. The design and materials of the supports make it possible to operate them in an environment with an aggressive degree of impact in climatic zones, where the ambient temperature drops to -55 ° C, seismicity reaches 9 points, and wind and ice loads correspond to VII and V regions according to SNiP2.01.07-85.


Currently, energy construction is actively using power transmission towers throughout Russia, as they are the most resistant to extremely low atmospheric temperatures and aggressive environmental influences. Unlike a wooden lighting pole, reinforced concrete products do not rot in a humid climate and can be installed both in the city and along highways, railways, in mountainous or wetlands and forests. Compared to metal products, racks SV 110-3.5 IV for poles of 10 kV transmission lines for non-aggressive and aggressive environments do not require regular technical inspection, they do not need to be periodically painted or galvanized to prevent corrosion or oxidation - concrete is pre-treated during molding with anti-corrosion and water-repellent additives.


In the production of power transmission towers, we use the latest production technologies to ensure the high quality of reinforced concrete products and maintain the performance of products for many years. Our rack products SV 110-3.5 IV for poles of 10 kV transmission lines for non-aggressive and aggressive environments comply with all standards and requirements of GOST.


Structurally, power transmission towers are an elongated rectilinear figure - a rack. Embedded parts for clamps, traverses and fasteners for fixing wires are provided in the body of the structure. The lower part of the support, if necessary, also has embedded parts for fastening to the foundation and other structures that serve to increase the stability and bearing capacity of the supports (slabs, crossbars).


Installation of rack products SV 110-3.5 IV for poles of 10 kV transmission lines for non-aggressive and aggressive environments begins with laying out the details of the pole along the route for its further assembly. Assembled on the ground, the structure of the power transmission line support is lifted to the design position with the help of a crane and installed in a cylindrical pit with filling the voids with a sand-gravel mixture. In soils with low bearing capacity, the fastening strength is achieved by fixing the supports with crossbars and installing them on special base plates. For fixing guy wires in the ground, anchor plates or other foundation structures are installed at the design distance from the support in accordance with the project.


Energy construction assumes that the products of the SV 110-3.5 IV rack for 10 kV transmission line supports for non-aggressive and aggressive environments are made only from high-strength heavy concrete with a compressive strength class of B30. Portland cement is used as a raw material for this, which has increased strength, frost resistance, corrosion resistance and low water permeability. Granite crushed stone, which is introduced into the composition of concrete, gives products additional stability and resistance to low temperatures and high humidity. The frame made of high-strength steel compensates for the fragility of concrete and increases the elasticity of the structure. In order for the supports to be resistant to external influences, they are compacted by vibration, due to which air cavities are removed, and the concrete mixture spreads evenly over the entire cross section.


The concrete of the pillars of the power transmission line supports is reinforced with prestressed reinforcement to give greater strength to the products. Reinforcement in the form of three-dimensional frames is carried out from bar steel of classes A-III, At-I, At-V and At-VI. All parts of the products of the SV 110-3.5 IV rack for 10 kV power transmission line supports for non-aggressive and aggressive reinforcement environments and embedded parts are pre-treated with anti-corrosion treatment and coated with polymer coatings.


Like any load-bearing structures, racks SV 110-3.5 IV for poles of 10 kV power transmission lines for non-aggressive and aggressive environments are subject to strict product quality checks. Power transmission line supports should not have cracks, except for shrinkage cracks, the width of which should not exceed 0.2 mm. Sinks should be no wider than 20 mm in width, chips - no more than 20 mm in depth. Maximum deviations of the geometric parameters of reinforced concrete supports should be no more than ± 60-80 mm in length, section - ± 6 mm. Deviations from the plane of the rack should be no more than 15 mm in any direction. Reinforcement exposure is strictly prohibited. The thickness of the protective layer of concrete to the reinforcement should not be less than the design by 3 mm.


The table shows the prices for our products (excluding delivery) subject to 100% prepayment. Our clients can use the discount system according to the quantity and cost of purchased products.

*This offer does not constitute a public offer


The guaranteed service life of a reinforced concrete rack is 50 years, which is many times greater. The guaranteed service life of a reinforced concrete rack is 50 years, which is many times longer than the time of using wooden counterparts. Despite their considerable weight, their delivery is not difficult due to the availability of special equipment and numerous methods of transportation.

Numerous technical advantages of the reinforced concrete rack made this type of product indispensable for the creation of power lines in any climatic conditions. Due to the high quality of the materials used and the latest production technologies, this type of pole, unlike wooden poles, is characterized by increased technical performance and the possibility of stable operation in conditions of high humidity, aggressive environments and low temperatures (up to -65 ° C)

Reinforced concrete racks by appointment:

intermediate free-standing and braced models
anchor different number of supports
terminal with internal connections
special and corner single and multi-strand
reinforced concrete racks

Support SV 110-3.5


Support SV-110-3.5 made of vibrated concrete with a reinforced steel backfill has precise dimensions and even shape. Special additives are added to the concrete used in the manufacture of products, it is treated with water-repellent, anti-corrosion agents. The design provides for special mortgages, to which clamps and traverses are fastened.

Support has high strength characteristics and is designed to hold wires during the operation of power lines, the voltage in which is from 6 to 10 kilovolts, which are used to organize lighting.

Stand SV-110-3.5 is the basis of a power transmission line support and can be successfully used for fixing overhead power lines, lighting fixtures on streets and squares, and for arranging highways. It provides a uniform tension of the wires fixed on the intermediate, branch and corner supports of the 10 kV overhead line. After installation, the necessary metal structures, specialized lighting equipment, an insulated system of self-supporting wires, a telecommunications cable, etc. are attached to the supports.
All products are checked for quality and therefore do not have cracks, shells, chips larger than the allowable standard. Products are certified, produced in compliance with all the subtleties of the technological process.
Due to the high quality of production, the racks are ideal for the terrain, which is characterized by a harsh environment. The use of modern equipment and the use of the latest reinforcement technology give the racks excellent frost-resistant and waterproof properties.

Numerous tests carried out indicate that the operation of reinforced concrete vibrated SV supports is possible in extreme conditions:

The strength of reinforced concrete supports SV 110 3.5, equipped with anchor plates, crossbars, clamps and used in the base of the racks, makes it possible to ensure their high reliability and stability in soils of any type.
Reinforced concrete racks are produced at our own production site in the city of Berezovsky, Sverdlovsk Region, using modern equipment with innovative technological solutions.

Production of reinforced concrete poles SV 110-3.5

Production of racks CB 110-3.5 in Moscow, Yekaterinburg, Perm and Tyumen.
The production capacities of the enterprise allow the production of more than 2,500 pieces of reinforced concrete pillars SV 110 3.5 per month.
Reinforced concrete supports are indispensable in the construction and overhaul of power transmission lines and are designed to accommodate and hold wires at a height regulated by the relevant state. standards. The pillars are based on a strong steel frame, located inside a concrete structure, made by centrifugation or vibration in order to maximize compaction and give it strength and resistance to negative factors. It is advantageous to buy a stand CB 110-35.5 from the manufacturer - the LLC PO Garantiya company.

You can buy a support, a stand CB 110-3.5 at OOO PO Garantiya at a price of 8,000 rubles per unit.


production site

Reinforced Concrete Products Plant LLC "PO "GARANTIYA"
Address: Sverdlovsk region. Berezovsky st. Western industrial area 21/a

How to get to the production:

Reinforced concrete vibrated poles for 0.4 ... 10 kV overhead lines TU 5863-007-00113557-94
Name Dimensions (LxWxH, mm) volume, m3 Weight, t Price for 1 unit with VAT, rub.
SV 110-5 11000x185/165x280/185 0,45 1,13 7581
SV 110-3.5 11000x185/165x280/185 0,45 1,13 7098
SV 95-2 9500x240/165x165/165 0,3 0,75 5285
SV 95-3 9500x240/165x165/165 0,3 0,75 5573

Racks reinforced concrete vibrated CB are designed for supports of overhead power lines. They have other names, such as lighting poles, or simply power poles. Our factory produces two types of CB racks, nine and a half and eleven meters long.

Racks CB 95 intended for high-voltage lines 0.4 ... 10 kV. If you need to connect a portable ground to these supports, then this can be done thanks to the conclusions of special contacts. During the repair and maintenance of overhead lines, this property of the SV supports increases the safety of work. Supports SV 95 differ from each other in the calculated bending moment. This parameter can be 2.0 tf/m and 3.0 tf/m. It is allowed to use CB racks both in non-aggressive and in aggressive environmental conditions. Design supports SV 95 designed in such a way that the rack has 4 grounding descents, which provide reliable grounding of the working fittings of the product. The strut CB 95-2, like the strut CB 95-3, has an upper end reinforced with prestressing reinforcement. At the end there is a steel plate that performs the functions of protection against destruction, increasing the service life of the CB support.

After stripping the finished product, metal end plates are welded to the four reinforcing bars of the SV support. A grounding conductor is welded to the mortgage loop and the bottom plate, and an outlet for portable grounding is attached to its end. If during the production of racks CB 95 the reinforcement is not prestressed, then end plates will be absent.

eleven meters racks CB 110 are also made from heavy concrete of B30 compression class. The frost resistance of concrete should not be less than two hundred cycles, and the water resistance index should be W6. For intended use in a hostile environment, supports SV 110 a protective coating must be applied to their lower part. It can be bitumen or mastic. This coating is applied directly in the factory to a length of up to three meters. Also, for aggressive environments, the diameter of the grounding lower conductor should be twelve millimeters, and the place of its welding should be protected with anti-corrosion varnish.

Installation of CB racks should be carried out only by qualified teams of installers. The supports are stored on a pre-leveled area, laying wooden blocks. The year of installation and serial number must be applied to each CB rack with indelible paint. The top of the support is lifted with the help of a truck crane, traverses are attached, a grounding slope is laid. At a distance of three meters from the ground line, a warning poster can be installed. Often mount special breaker cabinets. This is done in places where there is a risk of damage to the support by vehicles.

After preliminary marking, work on drilling the soil is underway. The depth of the hole will depend on the thickness and height of the installed SV supports, and its diameter should be twenty centimeters larger than that of these pillars. Next comes the actual installation of the racks. In order to achieve a strictly vertical position of the support during installation, it is placed on temporary struts. High-grade concrete is poured into the voids directly to ground level. After all the CB racks are fixed, it is necessary to make a control check of the position of each of them.